E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

70
STEP 3: Drive Reference and/or PID Setpoint via Serial Communication Controller
Bypass
Paremeter
1103
REF1 SELECT
DRIVE
CONTROL
PANEL
4010
SET POINT SEL
DRIVE
CONTROL
PANEL
STEP 4: BACnet Setup
Bypass
Paremeter
5311
DV PAR11
DRIVE ID
5317
DV PAR17
DRIVE ID
5011
BP PAR11
BYPASS ID
5017
BP PAR17
BYPASS ID
Note: See E-Clipse Bypass Configuration manual section Parameter Description for complete list of group 16 parameters and settings.
REQUIRED
STEP 5: CYCLE POWER
ALLOW TIME FOR DC BUS TO DISCHARGE. This is required for serial communication changes to
take effect
STEP 6: E-Clipse Bypass
View E-Clipse Bypass Parameter 53.08 UART ERROR. If 53.08 is incrementing up, check the
network configuration. (Trunk polarity, Baud rate, Parity, Noise on trunk, or Duplicate addresses).
View Parameter 53.07 CRC ERROR. If it is incrementing up, check protocol and noise on trunk.
View Parameter 53.09, it should be display "ON LINE". If 53.09 displays "IDLE", the drive is not
communicating with the controller, verify wiring.
Embedded Fieldbus and Fieldbus Adapters
DRIVE
SYSTEM
DRV & BYPASS
8
8
8
8
DRIVE
SYSTEM
DRV & BYPASS
Set DRIVE
Set DRIVE
BACnet device
BACnet device
ID
ID
Set DRIVE
Set DRIVE
BACnet device
BACnet device
ID
ID
N/A
Set BYPASS
BACnet device
ID
N/A
Set BYPASS
BACnet device
ID
E-Clipse Bypass Configurations for ACH550 Drives
Description
Selects the signal source for external reference
REF1 = COMM – Defines the fieldbus as the reference source.
SEE ACH550-01/02 User Manual for additional information
Defines the reference signal source for the PID controller.
Parameter has no significance when the PID regulator is by-
passed
8 = COMM – Fieldbus provides set point.
SEE ACH550-01/02 User Manual for additional information
Description
This parameter, together with 5317 sets the DRIVE BACnet
device object instance ID
For DRIVE ID's > 65,535 the ID = 5311's value + (10,000 x 5317)
This parameter, together with 5317 sets the BYPASS BACnet
device object instance ID
For BYPASS ID's > 65,535 the ID = 5311's value + (10,000 x
5317)