ABB ACH550 series User Manual page 58

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

56
Group 14
Code
Name
1401
RO1 SELECT
1402
R1 ON DLY
1403
R1 OFF DLY
1404
RO2 SELECT
1405
R2 ON DLY
1406
R2 OFF DLY
1407
RO3 SELECT
1408
R3 ON DLY
1409
R3 OFF DLY
1410
RO4 SELECT
Parameter Descriptions
Resolution
Range
1
0 = NOT SEL
1 = SYS READY
2 = SYS RUNNING
3 = SYS STARTED
4 = BYPASS SEL
5 = BYPASS RUN
6 = BYPASS FLT
7 = BYP NOT FLT
8 = BYPASS ALRM
9 = DRIVE FAULT
10 = DRV NOT FLT
11 = DRIVE ALARM
12 = OVERRIDE
13 = BYPASS HAND
14 = BYPASS OFF
15 = BYPASS AUTO
16 = COMM CTRL
17 = SYS ALARM
18 = BYP FLT/ALM
19 = BYP OVERLD
20 = BYP UNDERLD
21 = PCB OVERTMP
22 = SYS UNDERLD
23 = SYSTEM FLT
24 = SYS FLT/ALM
25 = SYS EXT CTL
26 = SYS OVERLD
27 = CONTACT FLT
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
1
See RO 1 Select.
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
1
See RO 1 Select.
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
1
See RO 1 Select.
E-Clipse Bypass Configurations for ACH550 Drives
Default
BYP NOT
Selects function for digital output.
FLT
Define the event or condition that
(7)
activates relay 1.
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
SYS
RUNNING
(2)
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
SYS
STARTED
(3)
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
BYPASS
SEL
(4)
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents