1MRS755001
3.4.
COM600 series 5.1
Sequence Control Configuration Manual

Adding logical nodes for a sequence

At a minimum, each added sequence logical device should have the predefined SEQG-
GIO1 and STEPGGIO1 logical nodes with data objects. The SEQGGIO logical node
has data objects related to the entire sequence functionality, whereas the STEPGGIO
logical node has data objects for a step in the sequence. The predefined logical nodes
and data attributes for a sequence logical device are described in Table 3.4-1.
The description parameter of the data objects in the logical
devices is used in event reporting for sequence execution. To
be able to identify the step number involved, edit the
description parameter of the "St" data object for a STEPGGIO
logical node.
Additional STEPGGIO logical nodes should be added for a sequence with multiple steps.
Table 3.4-1 Predefined logical nodes and data objects for a sequence logical device
Logical node name
Data object name
SEQGGIO1
St
Str
Auto
StepExec
OnStepErr
STEPGGIO1
St
To add additional logical node objects:
1. Right-click the sequence logical device and select New > Communication >
Sequence Step LN.
Figure 3.4-1 Adding a logical node for a sequence logical device
2. Edit the description parameter for the "St" data object in the added STEPGGIO1
logical node for additional clarity.
Data object type
Data object descrip-
tion
INS
State
SPC
Control
SPC
Execution mode
SPC
Manual mode acknow-
ledgement
SPC
On step error
INS
Step (number) state
SAB600_SC_PLC_LN.png