Totalizer Count Rate
Automatic – the recorder has calculated the count rate automatically. No further
adjustment is possible.
Manual
– the count rate must be calculated manually (see page 36). Use the
and
00.0000 to 99.9999 in 0.0001 increments.
Note. To configure the totalizer for Automatic count rate calculation:
1. Ensure that the unit of measurement (Channel Units) selected for the channel to which the
totalizer is assigned is a volumetric unit (i.e. quantity per unit of time, for example gallons
per hour) – see Section 3.5, page 24.
2. Enter the required Totalizer unit of measurement (Totalizer Units) – see previous page.
If the recorder holds the relationship data between the selected measurement and totalizer units,
Automatic is displayed under the count rate to indicate that it has been set automatically.
Totalizer Cut Off
Set the value, in engineering units, at which the totalizer is to stop counting.
Totalizer Preset Value
Set the value, in engineering units, from which the totalizer is to start counting and the value that
is applied when the totalizer is reset.
Totalizer Predetermined Value
Set the value, in engineering units, at which the totalizer stops or wraps.
Continued on next page.
keys to enter the calculated count rate in pulses per second, from
3 Configuration
,