P1, K
P2, L
Figure 6.10. Back-up generator: CT connection (for one phase)
6.5.

Precautions with capacitors

In the presence of power capacitors (LV or MV), harmonics below the
resonance frequency of the capacitor bank should not be handled by the filter
to avoid any risk of resonance. Those harmonics have to be deselected (see
chapter 10 on programming the filter).
Networks where the PQFA is installed have large harmonic content and it is
highly recommended that capacitor banks be fitted with detuning reactors.
The harmonics below the tuning frequency of the bank have also to be
deselected.
The following table indicates the harmonics to be deselected for main types of
detuned banks.
Detuned bank type Harmonics to
5.67%
6%
7%
14%
For other types of detuned bank or in the case of plain capacitors, please
contact your ABB Service provider to evaluate the resonance frequency and
the harmonics to be deselected.
G
S1, k
S2, l
P1, K
P2, L
Asea Brown Boveri Jumet S.A.
PQFA Instructions Manual
P1
P2
S1, k
P1
S2, l
P2
be deselected
2, 3, 4.
2, 3, 4.
2, 3.
2.
k
S1
L
S2
PQF
43