ABB PQFA Instruction Manual page 93

Power quality filter
Table of Contents

Advertisement

Error
Error message
code
4
DC overvoltage
5
Connection
fault
6
Power
fault
7
Control
fault
8
CAN bus fault
16
DSP pgm
corrupted
32
Watchdog
timeout
Possible causes
DC voltage on DC bus
reaches
levels
Flat cable between
? ?
the control rack and
IGBT
disconnected
wrongly connected.
? ?
Module
setting
A112
correspond
number of modules
really present.
? ?
The jumpers on the
last domino board
are missing or are on
the wrong domino.
supply
One
of
the
power supplies is out of
service.
board
The microcontroller is
not working properly.
The internal
communication bus of
the PQFA is not working
properly.
DSP program corrupted
Software in
unpredictable state.
Asea Brown Boveri Jumet S.A.
PQFA Instructions Manual
Actions
? ?
Check DC capacitors
Inspect ? 15V power
unacceptable
? ?
supply (U100)
? ?
Inspect
current
(B101/102/103)
? ?
Inspect visually DC
voltage divider and
wiring
? ?
Check
connections
? ?
driver
is
Verify that only the
or
domino board of the
last power module is
number
fitted with jumpers
? ?
on
board
Check the number of
does
not
modules set on the
to
the
controller board A112
? ?
auxiliary
Check that no red
LED is on the control
rack (except LED 3 of
A111). If yes, call
your
provider.
? ?
Check fuses of power
supplies
Contact
your
provider.
Contact
your
provider.
Contact
your
provider.
Contact
your
provider.
internal
sensor
flat
cable
ABB
service
immediately
ABB
service
immediately
ABB
service
immediately
ABB
service
immediately
ABB
service
93