Siemens S5-135U/155U System Manual page 116

Siemens network card system manual
Table of Contents

Advertisement

Central Controllers and Expansion Units Power Supply Units
Behavior Upon
Failure of Fans
Failure Indication
If a fan fails (its speed decreases) a fault is indicated, i.e. the red LED
assigned to the fan lights up:
If a Fan Fails
If a fan fails, the following takes place:
1
2
3
4
If Another Fan
If another fan fails, the following takes place:
Fails
5
6
7
8
Resetting the Fault
When the fault has been cleared (faulty fan replaced, filter mat replaced),
Message
you can reset the fault messages by pressing the Reset button.
Caution
!
You can suppress the shutdown of the power supply by opening jumper F-R.
In this case, you must ensure that the power supply is switched off after 60
secs at the latest. This can be achieved with a time relay, for example. This
prevents modules from overheating and being damaged.
4-50
"Fan 1" LED = left fan failed
"Fan 2" LED = middle fan failed
"Fan 3" LED = right fan failed
Stage
A fan fails.
Result:
– The red LED assigned to the fan lights up.
Contacts 9 and 10 in the "Warning" relay are closed.
The faulty fan is switched off.
The other two fans operate at increased voltage and an audibly higher
speed.
Stage
Another fan fails.
Result:
– The red LED assigned to the fan lights up.
Contacts 12 and 13 in the "Alarm" relay are closed.
Result:
– "Alarm" LED lights up.
– Two "Fan"-red LEDs light up.
A data save routine is started and, with the appropriate jumper setting, an
output inhibit is issued.
The power supply switches off, with the appropriate jumper setting.
Description
Description
System Manual
C79000-G8576-C199-06