CPUs, Memory Cards, Memory Submodules, Interface Submodules
5.11.7

Technical Specifications of the Interface Submodules

Important for the USA and Canada
The following approvals have been obtained:
Degree of protection
Ambient temperature
in operation
for transporation and storage
Relative humidity
Supply voltage
Transmission rate
PG submodule
V.24 submodule
TTY submodule
RS422-A/485 submodule
SINEC L1 submodule
Front connector, female
PG, RS422 A/485, SINEC L1
submodule
V.24, TTY submodule
Transmission cable
Line length
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
Current consumption at 5 V/24 V
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
Design
Dimensions (WxHxD)
Weight
per interface submodule
5-122
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
IP 00
0 to +55 C
– 40 to +70 C
95% max. at 25 C, no condensation
5V
5%
24V + 25%/– 17%
9 600 bps fixed
19 200 bps max.
9600 bps max.
19 200 bps max.
(when submodule is used in a CPU)
9600 bps fixed
15-pin Cannon
25-pin Cannon
Shielded four-wire line (five-wire line for
RS422 A) with braided shield and metal
housing on connector, grounding required at
both ends.
1000 m max.
16 m max.
1000 m max.
1200 m max.
1000 m max.
5 V
40 mA max.
0.2 A max.
0.1 A max.
0.5 A max.
170 mA max.
16.3 mm x 60 mm x 102.7 mm
Approx. 0.1 kg
C79000-G8576-C199-06
24 V
380 A
60 mA
100 mA
System Manual