Measuring point-related error signal
– for overflow
– for broken wire
Max. permissible input voltage without destruction
Interference suppression for f = n x (50/60 Hz
– with common-mode interference
– with differential-mode interference
Error referred to rated value
– linearity
– tolerance
– polarity reversal error
– temperature error
Error caused by cards with input range
1 V/
5 V /
10 V
20 mA/4 to 20 mA
Setting the Mode
You select the desired mode of the analog input module by setting mode
switches I and II according to the following table.
Note that all the rockers of both mode switches marked with a dot must be
set, and some functions are defined by several rockers (e.g. 8- to 16-channel
operation, broken wire signal for 8 or 16 channels).
To activate the desired modes, press the rockers down on the side marked
with a dot.
System Manual
C79000-G8576-C199-06
Analog Input/Output Modules
Yes
Yes, configurable
(at
50 mV,
500 mV and Pt 100)
18 V; 75 V for 1 ms max. and duty ratio 1:20
1 %)
86 dB, but
1 V max.
40 dB, noise voltage amplitude
but 100 % max. of measuring range
referred to peak value
1 unit
1 unit
1 unit
–4
1 x 10
/K
–3
2 x 10
; TC =
–3
10
; TC =
5 x 10
–5
10 x 10
/K
–5
/K
9-73