4.3.6
Technical Specifications of the Power Supply Units
Important for the USA and Canada
The following approval has been obtained:
UL-Recognition-Mark (for USA)
Underwriters Laboratories (UL) to
Standard UL 508, Report E 143289
CUL-Recognition-Mark (for Canada) to
Canadian National Standard C 22.2, No. 142, Report E 143289
Safety Specifications
Shock protection
Data for EMC in the installed state
Safe isolation
Input
Rated input voltage
Rated input frequency
Input current I
i/p
at rated loed and rated V
= 120V
i/p
= 230V
Peak inrush current I
i/p max
I t value of inrush current
Efficiency at rated load (with fans) and V
230/120 V AC
Max. heat dissipation at rated load at
V
, V
, V
(with fans)
o/p1
o/p2
o/p3
Efficiency at rated load (without fans) and
V
230/120 V AC
i/p
Max. heat dissipation (without fans)
Stored energy time during power failure at
rated load and
V
187/93 V AC (adjustable)
i/p
Input fuse
External battery supply
System Manual
C79000-G8576-C199-06
Central Controllers and Expansion Units Power Supply Units
6ES5 955-3LC42
The power supply units comply with safety specifications VDE 0805 /
EN 60950 / IEC 950 / VDE 0160 and VDE 0106 Part 101.
only insured in the installed state
see technical specifications of the S5-135U/155U CC
is ensured.
120 V (93-132 V) AC
230 V (187-264 V) AC
50/60 Hz (47-63 Hz)
2.5 A
rms
1.5 A
rms
26 A for 2 s, otherwise < 5 A
(repetition rate 100 secs)
4 A s
> 0.63
i/p
80 W
0.70
53 W
>20 ms
20 ms
5 ms
Wickmann G 19343-T4A/250V,
500 A s
4.5 V
6ES5 955-3LF42
120 V (93-132 V) AC
230 V (187-264 V) AC
50/60 Hz (47-63 Hz)
4.5 A
rms
2.6 A
rms
25 A for 2 ms
(repetition rate 100 secs)
5.2 A s
> 0.68
147 W
0.71
123 W
>20 ms
20 ms
5 ms
Wickmann G 19340-8A/250V,
200 A s
4.5 V