Digital Input/Output Modules
8.4.11
6ES5 453-4UA12 Digital Output Module
Rated supply voltage L+
Number of outputs (decoupled via diodes)
Isolation
Range for supply voltage
Fusing
Output voltage
for logic 1:
for logic 0:
Switching current (resistive, inductive load)
Residual current at logic 0
Switching current for lamps
Switching frequency
with resistive load
with inductive load
Breaking voltage (inductive)
Total switching current
Coincidence factor (total load capability)
ventilated
not ventilated
Permissible line length
Power supply
Digital section from system bus
Power dissipation (rated operation)
Enable input (F+/F–)
Rated input voltage
Input voltage
for logic 1
for logic 0
Rated input current
Permissible line length
Short-circuit monitoring
Indicator for signaling output (H+, H–), floating
Output voltage as L+ switch
for logic 1
for logic 0
Switching current
Voltage test to VDE 0160
Mechanical specifications
Dimensions (W x H x D)
Weight
1)
Short-circuit protection responds with line resistance
2)
One digital input is permissible as minimum load.
8-52
24 V DC
16, short-circuit protected
Yes, 16 outputs
20 to 30 V DC
16 x 2.5 A, slow
(L+)-Switch
L+ – 2.5 V min.
(L–)-Switch
2.5 V max.
(L+)-Switch
3 V max.
(L–)-Switch
L+ – 3 V min.
10 mA to 2.0 A
1 mA max.
0.45 A max. (10 W)
100 Hz max.
0.2 Hz max. at 1 A; 0.1 Hz at 2 A
Limited to L+ – 47 V
4 A max. 8 outputs
100 %
25 %; 50 % to 20
400 m max., unshielded
5 V, 120 mA typical
49.0 W
24 V DC
13 to 33 V
– 33 to 5 V
5 mA
200 m max.
Red LED for 16 outputs
L+ – 5 V min.
3 V max.
10 mA max., short-circuit protected
Between two groups: 1250 V AC
Between group and ground point: 1250 V AC
40 mm x 255 mm x 195 mm
Approx. 0.6 kg
3.6 ohms.
1)
2)
o
C
System Manual
C79000-G8576-C199-06

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uS5-155u