Figure 3-8 Typical Motor Rating Plate Example - Siemens Micromaster 440 Operating Instructions Manual

0.12 kw - 250 kw
Hide thumbs Also See for Micromaster 440:
Table of Contents

Advertisement

Issue 12/02
Motor data for parameterization
Figure 3-8
NOTICE
! P0308 is only visible if P0003 ≥ 2. Depending on the settings for parameter
P0100, only P 0308 or P0309 is displayed.
! P0307 indicates kW or HP depending upon the setting of P0100. For detailed
information, please see the Parameter List.
! Changing motor parameters is only possible with P0010 = 1 (factory setting)
and P0004 = 0 or 3.
! Ensure that the inverter is configured correctly to the motor.
! Observe the motor's star/delta connection arrangement!
3.2.4
Reset to Factory default
To reset all parameters to the factory default settings; the following parameters
should be set as follows (BOP, AOP or Communication Option needed):
1. Set P0010 = 30
2. Set P0970 = 1
NOTE
The reset process can take up to 3 minutes to complete.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Typical Motor Rating Plate Example
(The details given on the rating plate are only examples)
3 Commissioning
55