Topology Example: Parallel Motor Modules In Vector Control - Siemens SINAMICS S120 Function Manual

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

13.11.2

Topology example: Parallel Motor Modules in vector control

Drive line-up with two parallel-connected Line Modules and Motor Modules in the chassis format of
the same type
Parallel-connected Line Modules in the chassis format and Motor Modules in the chassis
format of the same type can be connected to a DRIVE-CLiQ socket of the Control Unit.
In the following diagram, two Active Line Modules and two Motor Modules are connected to
the X100 or X101 socket.
You can find additional notes in Chapter "Parallel connection of power units" in the
SINAMICS S120 Function Manual.
Note
The offline topology automatically generated in the STARTER commissioning tool must be
manually modified, if this topology was wired.
Figure 13-22 Drive line-up with parallel-connected power units in the chassis format
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Basic information about the drive system
13.11 Supported sample topologies
877