Siemens SINAMICS S120 Function Manual page 770

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Communication
11.5 Communication services and used port numbers
Report
PTCP
Precision
Transparent
Clock Protocol
PROFINET IO
data
PROFINET
Context Manager
Connection-oriented communication protocols
HTTP
Hypertext
transfer protocol
ISO on TCP
(according to
RFC 1006)
770
Port
(2) Link layer
number
(4) Transport layer
Not relevant (2) Ethernet II and
IEEE 802.1Q and
Ethertype 0x8892
(PROFINET)
Not relevant (2) Ethernet II and
IEEE 802.1Q and
Ethertype 0x8892
(PROFINET)
34964
(4) UDP
80
(4) TCP
102
(4) TCP
Function
Description
PROFINET
PTC enables a time
delay measurement
send clock and
time
between RJ45 ports and
synchronisation
therefore the send cycle
, based on
synchronization and time
IEEE 1588
synchronization.
PTCP uses the special
multicast MAC address:
xx-xx-xx-01-0E-CF,
xx-xx-xx =
Organizationally Unique
Identifier
PROFINET
The PROFINET IO
Cyclic IO data
telegrams are used to
transfer
cyclically transfer I/O
data between the
PROFINET IO controller
and IO devices via
Ethernet.
PROFINET
The PROFINET context
connection less
manager provides an
RPC
endpoint mapper in
order to establish an
application relationship
(PROFINET AR).
Hypertext
HTTP is used for the
transfer
communication with the
protocol
CU internal Web server.
Is open in the delivery
state and can be
deactivated.
ISO-on-TCP
ISO on TCP (according
protocol
to RFC 1006) is used for
the message-oriented
data exchange to a
remote CPU, WinAC or
devices of other
suppliers.
Communication with ES,
HMI, etc.
Is open in the delivery
state and is always
required.
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4