Examples of when to carry out forced dormant error detection:
● When the drives are at a standstill after the system has been switched on (POWER ON).
● When the protective door is opened.
● At defined intervals (e.g. every 8 hours).
● In automatic mode (time and event dependent).
● The maximum time interval is one year (8760 hours).
Test stop / forced dormant error detection can be automatically executed at POWER ON.
● If the test stop / forced dormant error detection as well as the test of the F-DO for the
● If the test stop / forced dormant error detection of the F-DI and F-DO of the TM54F is to
● If you have parameterized the test stop / forced dormant error detection for POWER ON,
● If the automatically initiated function cannot be correctly completed as a result of a
● After the test stop / forced dormant error detection has been successfully executed, the
● Timer p9659 is automatically reset as a result of the test stop / forced dormant error
● The automatic test stop / forced dormant error detection for POWER ON does not
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
CU310-2 are to be executed automatically, then set p9507.6 = 1. When testing the F-DO
of the CU310-2, you must parameterize p10042 and activate the test in p10046.
be executed automatically, then set p10048 = 1.
you can still initiate a test stop / forced dormant error detection at any time through the
application.
problem (e.g. communication failure), then after the problem has been resolved, the
function is automatically restarted.
converter goes into the "Ready" state.
detection.
influence the Safety Integrated functions.
Safety Integrated basic functions
10.2 General information
587