Commissioning steps:
1. Connect the line contactor control contact to DI/DO 8.
2. Parameterize DI/DO 8 as output (p0728.8 = 1).
3. Assign parameter p0738 the control signal for the line contactor r0863.1.
4. Connect the line contactor feedback contact to DI/DO 9.
5. Assign parameter p0860 an inverted input signal r0723.9.
6. Enter the monitoring time for the line contactor (100 ms) in p0861.
Line contactor behavior for Safe Torque Off (STO)
If the Safety Integrated function initiates an STO, the line contactor opens automatically.
If, however, the line contactor should remain closed when the STO is initiated, make the
following setting:
1. Set p0869 = 1.
2. Use p0867 to specify how long the line contactor should remain closed after initiating the
Function diagrams (see SINAMICS S120/S150 List Manual)
• 8934
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p0860
• r0863.1
• p0867
• p0869
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Note
The current-carrying capacity of the digital output must be observed (see SINAMICS
S120 Control Units and Supplementary System Components Manual). A contactor relay
may be required!
STO.
Active Infeed - Missing enables, line contactor control
BI: Line contactor, feedback signal
CO/BO: Drive coupling status word / control word
Power section main contactor hold time after OFF1
Configuration sequence control
Infeed
2.4 Line contactor control
53