8.11.4
ESR responses
8.11.4.1
Extended stopping
In the case of a fault, the objective is to stop the drive in a defined fashion. The stopping
method is used as long as the drive is still capable of functioning. The function is
parameterized and operates on an axis-specific basis. Axes are not coupled.
Configuring the "Extended stop" response
1. Configure the stopping response with the parameter setting p0888 = 1 (N-set) or
2. Set the time in parameter p0892 for which the last setpoint from r1438 and the last actual
3. Select the OFF ramp with parameter p0891.
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
p0888 = 4 (N-actual).
value from r0063 are frozen before braking is initiated.
Figure 8-28
OFF ramp with timer
Function modules
8.11 Extended stop and retract
537