Open the refresh parameter setting window, and make settings as below.
Project window [Parameter] [Network Parameter] [Ethernet/CC IE/MELSECNET]
5.
Write the set parameters into the CPU module of the master station, and reset the CPU module or
power off and on the programmable controller.
[Online] [Write to PLC]
(b) Settings on the remote I/O station
1.
Create a project in GX Works2.
For "Series", select "QCPU (Q mode)". For "Type", select "QJ72LP25/QJ72BR15(RemoteI/O)".
[Project] [New]