Building Technologies
Fire Safety
1 Bare length for 20-pin connector
2 Press screwdriver (width of blade
2.5 mm) as far as stop position to
open spring contact
3 Fit 20-pin connector on to
FDCL221-M
4 Bare length for 4-pin
FDnet/C-NET plug
5 2-loop operation:
FDnet/C-NET loop 1
Connect multi line separator module as shown in connection diagram and place
jumpers according to use.
Note the following when connecting the multi line separator module:
●
Only connect one wire per terminal.
●
If using shielded FDnet/C-NET cables, connect cable shielding to connection
terminal DBZ1190-AB. The shielding must not touch any external ground
potentials or metal parts.
●
Secure cables on module carrier with cable ties.
●
Only connect one sub-stub between two FDnet/C-NET devices. If you need to
connect more than one sub-stub always connect a line separator between the
sub-stubs.
●
Press orange contact opening with screwdriver (width of blade 2.5 mm) when
inserting wire into socket strip.
●
Press orange contact opening with screwdriver to loosen connection line from
socket strip.
Place nine line separators, each with an ID number, between sub-stub
connections. Self-adhesive tear-off labels are available on the FDCL221-M for your
system documentation (see following figure).
Figure 13: Tear-off labels
●
Stick appropriate tear-off label to your system documentation.
●
Remove all unused tear-off labels from FDCL221-M!
See also
2 Adjustment elements [➙ 19]
2 Function [➙ 19]
Mounting / Installation
Installation and connection diagram
6 2-loop operation:
FDnet/C-NET loop 2
7 1 loop operation:
FDnet/C-NET
8 Configuration with jumpers:
- 1-loop operation (default)
- 2-loop operation
9 Tear-off labels
A6V10224006_g_en_--
5
33 | 42