Line separator
(per separator)
External alarm indicators
Connections
Ambient conditions
Building Technologies
Fire Safety
Line voltage:
●
Nominal
●
Minimum
●
Maximum
Voltage at which the separator
opens:
●
Minimum
●
Maximum
Permanent current when switches
are closed
Switching current (e.g., in the
event of a short-circuit)
Leakage current when switches
are open
Serial impedance when switches
are closed
When operated on the FDnet/C-NET, the line separator is closed via an
actuation signal from the control panel. Required line voltage: DC 12...33 V
(normal range)
Number of external alarm
indicators that can be connected
Detector line:
●
Design
●
Cable cross section
●
Bare length
Sub-stubs:
●
Design
●
Cable cross section
●
Bare length
Operating temperature
Storage temperature
Air humidity (non-condensing)
Protection category (IEC 60529):
●
Without housing
●
With housing FDCH221,
screwed
Electromagnetic compatibility:
●
1 MHz...2 GHz
Specifications
Technical data
DC 32 V (= V
)
nom
DC 12 V (= V
)
min
DC 33 V (= V
)
max
DC 7.5 V (= V
)
SO min
DC 10.5 V (= V
)
SO max
Max. 1.5 A (= I
)
C max
Max. 2 A (= I
)
S max
Max. 1 mA (= I
)
L max
Max. 0.4 Ω (= Z
)
C max
None
Screw terminals on plug
0.2...1.5 mm
2
6 mm
Socket strip
0.2...1.5 mm
2
10 mm
-25...+70 °C
-30...+75 °C
≤95 % rel.
IP30
IP65
10 V/m
8
37 | 42
A6V10224006_g_en_--