Planning - Siemens FDCL221-M Technical Manual

Multi line separator module
Hide thumbs Also See for FDCL221-M:
Table of Contents

Advertisement

4 Planning

Building Technologies
Fire Safety
Unique detector line topology recognition is ensured if at least one device with a
separating function is present between two sub-stub lines. In this case a line
separator.
Station
Figure 6: Line separator between two sub-stubs
If several sub-stub lines are to be activated on one FDnet/C-NET loop, failure of
large numbers of devices must be prevented in the event of a line short-circuit. In
this regard the national regulations must be observed.
From a FDnet/C-NET communication point of view, the line separator is a normal
line participant which occupies one bus address and is visible in the line topology.
Rules for the branching of a sub-stub from a loop
Only one sub-stub is permitted between two FDnet/C-NET devices.
One sub-stub is permitted at the start and end of the loop respectively,
between the connection terminals of the fire control panel and the first line
device.
If there is more than one sub-stub between two FDnet/C-NET devices, a line
separator must be fitted between the sub-stubs.
The following figure shows the common variants of a detector line which has been
modified from a collective detector line to a FDnet/C-NET detector line, on which
FDnet/C-NET devices (Tr/Ts) are installed with an integrated line separator
function. The outgoing sub-stub lines are directly connected to the multi line
separator modules FDCL221-M without a distributor terminal.
Planning
4
Accessories
FDCL221
FDCL221-M
25 | 42
A6V10224006_g_en_--
2018-10-25

Advertisement

Table of Contents
loading

Table of Contents