5.
Set the items in "Basic setting" of "Module Parameter" as follows.
[Navigation window]  [Parameter]  [Module Information]  [RJ51AW12AL]  [Module Parameter]  [Basic setting]
6.
Write the set parameters to the remote head module on the intelligent device station. Then, reset the remote head
module or power off and on the system.
[Online]  [Write to PLC]
In this example, default values are used for parameters that are not shown above. For the parameters, refer to
the following.
•  MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual (Application)
• Page 48 PARAMETER SETTINGS
Settings in the slave modules
Write addresses to slave modules and register them with the RJ51AW12AL.
■Address setting
Write addresses to slave modules with an address writer.
• Output ASLINKER: Address 0 (ID: 0000H)
• Input ASLINKER: Address 0 (ID: 0200H)
■Automatic address detection
Keep pressing the SET switch on the RJ51AW12AL until the SET LED turns on.
When the SET LED flashes and then turns off, it indicates that the registration of IDs (addresses) has been completed.
Appendix 5 When Connecting the Module to a Remote Head Module