Bit Transmission; Word Transmission - Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual

Master module
Table of Contents

Advertisement

Bit transmission

In bit transmission, I/O data of up to 512 bits (input 256 bits, output 256 bits) is exchanged between the RJ51AW12AL and a
slave module.
Transmission setting
Set the number of bit data points to be transmitted in "Basic setting" of the engineering tool.
[Navigation window]  [Parameter]  [Module Information]  [RJ51AW12AL]  [Basic setting]
For details on the setting window, refer to the following.
Page 49 Bit data setting

Word transmission

In word transmission, I/O data of up to 1024 words (input 512 words, output 512 words) is exchanged between the
RJ51AW12AL and a slave module.
• To execute word transmission, configure a system only with slave modules that support word data.
Communications cannot be established between the slave module that does not support word data and the
RJ51AW12AL that is performing word transmission.
• To see whether the slave modules support word transmission, refer to their manual (manufactured by
Anywire Corporation).
1 FUNCTIONS
1.1 AnyWireASLINK Transmission