Parameter access
The operating procedure for parameter access is as follows.
■To read parameters
1.
Set the access method.
Store 0000H (read) in 'Parameter access setting' (Un\G10320).
2.
Set the access target ID.
Store the access target ID in 'Parameter access target module ID specification' (Un\G10321).
ID
0000H to 00FEH
0200H to 02FEH
0400H to 05FEH
0600H to 07FEH
3.
Turn off and on 'Parameter access request command for the slave module' (Y10).
At this time, 'Parameter access completion flag' (X11) turns off. In addition, 'Parameter accessing flag (with handshake)' (XB)
turns on.
4.
When the parameter access is completed, 'Parameter access completion flag' (X11) automatically turns on.
5.
Turn on and off 'Parameter access request command for the slave module' (Y10).
6.
When 'Parameter access completion flag' (X11) turns on and the following signals are turned off, 'Parameter accessing
flag (with handshake)' (XB) turns off.
• 'Parameter access request command for the slave module' (Y10)
• 'Parameter batch read command for the slave module' (Y11)
• 'Parameter batch write command for the slave module' (Y12)
7.
The read parameters are stored in the following location of each ID.
Device parameter in 'Parameter storage area' (Un\G12288 to Un\G12335)
*1 Buffer memory addresses when one slave module is connected. For details, refer to the following.
Page 107 Parameter storage area
1 FUNCTIONS
34
1.12 Slave Module Parameter Read/Write
Description
ID of a bit output slave module
ID of a bit input slave module or bit I/O combined slave module
ID of a word output slave module
ID of a word input slave module or word I/O combined slave module
*1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r seriesMelsec iq anywireaslink rj51aw12al

Table of Contents