Parameter access completion flag: X11
This signal turns on and off in any of the following cases and turns off and on when the relevant operation has completed.
• During the parameter access
• During the easy replacement for one slave module
• During the AnyWireASLINK version compatibility inspection
Parameter access error: X12
This signal turns on when an error occurs in the parameter access.
The latest error codes are stored in 'Latest error code storage area' (Un\G10256) and the target IDs of the error codes are
stored in 'Latest error ID storage area' (Un\G10257).
■Turning off of 'Parameter access error' (X12)
After the error is cleared, execute any of the following operations. Until then, 'Parameter access error' (X12) remains on.
• Reset the CPU module or power off and on the system.
• Turn on and off 'Error flag clear command' (Y0).
For how to eliminate the parameter access error, refer to the following.
Page 80 List of Error Codes
*1 If the error status automatic recovery function is enabled, this signal turns automatically off.
Automatic address detection flag: X14
The signal remains on from a start of execution of automatic address detection to the end of the execution.
Overlap address inspection flag: X15
The signal remains on from a start of execution of same address used check to the end of the execution.
One slave module changing flag: X16
This flag turns on during the slave module replacement using the easy replacement function for one slave module.
Slave module replacement completion flag: X17
This flag turns on when 'One slave module changing flag' (X16) turns off during the slave module replacement using the easy
replacement function for one slave module.
■Turning off of 'Slave module replacement completion flag' (X17)
'Slave module replacement completion flag' (X17) is on for five seconds and then turns off.