Communication over CANopen
6.7 Integrating the inverter into CANopen
Modified Node ID or activate baud rate
Procedure
To activate the changed bus address or baud rate, proceed as follows:
1. Switch off the inverter supply voltage.
2. Wait until all LEDs on the inverter go dark.
3. Switch on the inverter supply voltage again.
Your settings become active after switching on.
This means that you changed the settings
6.7.3

Setting the monitoring of the communication

To monitor the communication, use one of the following methods:
• Node guarding / life guarding
• Heartbeat
Node guarding / life guarding
Principle of operation
● Node guarding:
Is always active if heartbeat is not activated (p8606 = 0). Node guarding means the
master sends monitoring queries to the inverter which then answers.
The inverter does not monitor the communication. Set the responses to a bus failure in
the master.
● Life guarding:
is active if you use p8604.0 and p8604.1 to set a lifetime ≠ 0.
Life Guarding means that the inverter monitors the master's monitoring query and reports
fault F8700 (A) with fault value 2, if a life guarding protocol (life guarding event) is not
received within the lifetime. Set additional responses to a bus failure in the master.
Calculate value for lifetime
Life time = guard time in milliseconds (p8604.0) * life time factor (p8604.1)
196
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Fieldbuses