Siemens SINAMICS G110M Function Manual page 89

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Drive Object, Instance Number: 2A hex
Supported services
Class
• Get Attribute single
Table 4- 13
No.
1
2
3
Table 4- 14
No.
3
4
6
7
8
9
10
15
16
17
18
19
20
21
22
29
Fieldbuses
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Class Attribute
Service
Type
Name
get
UINT16
Revision
get
UINT16
Max Instance
get
UINT16
Num of Instances
Instance Attribute
Service
Type
Name
get
Bool
At reference
get, set Bool
Net_reference
get
UINT8
Drive_Mode
get
INT
Speed Actual
get, set INT
Speed Ref
get
INT
Current Actual
get, set INT
Current limit
get
INT
Power Actual
get
INT
Input voltage
get
INT
Output voltage
get, set UINT16
AccelTime
get, set UINT16
DecelTime
get, set UINT16
Low Speed Lim
get, set UINT16
High Speed Lim
get, set SINT
Speed Scale
get
Bool
Ref From Net
Communication via EtherNet/IP
Instance
• Get Attribute single
• Set Attribute single
Value/explanation
r2197.4
1: |n_act | ≥ n_set
0: Otherwise
Internal
0: Local
1: Network
p1300 manufacturer-specific, see following table
Main actual value, see speed units
Main setpoint, see speed units
r0027 absolute current actual value, smoothed
p0323 maximum motor current
r0032 actual active power smoothed
r0025 output voltage smoothed
r0072 output voltage
p1120 ramp-function generator ramp-up time
p1121 ramp-function generator, ramp-down time
p1080 minimum speed
p1082 maximum speed
p8982 Ethernet/IP ODVA speed scaling
Internal - display of Net_Reference
0: Local
1: Network
4.5 Supported objects
89