Test Mode - Siemens SITRANS DA400 Operating Instructions Manual

Process monitoring sitrans da400 for oscillating positive displacement pumps with protection against explosion
Table of Contents

Advertisement

Operation
6.3 Measuring menu
4. Briefly press the <MEAS> button. This returns you to the measuring menu.
5. Setting the measurement channel
6. Using the
7. Check whether the alarms are displayed accordingly in the digital display.
8. Make sure that the correct digital output is de-energized.
9. Switch to the measurement mode to exit the simulation mode
10. Using the
11. Briefly press the <MEAS> button. This returns you to the measuring menu.
Note
Exiting the simulation mode
The simulation mode is not automatically ended. Exit the simulation mode as described
above.
Note
Timers
If pre or main alarms are set in simulation mode, the timers count the trace function. If
necessary, set the counters back manually.
6.3.4.3

Test mode

Introduction
Test mode is used to check whether:
● The acoustic emission sensor is assigned to the correct acoustic channel.
● The acoustic emission sensor is functioning.
In test mode, the acoustic emission sensor is sensitive to both temporary knocking noise as
well as permanent flow-generated noise. The maximum sound pressure level measured is
saved and displayed.
Condition
The measurement channel must be in test mode. The measurement channel is in test mode
if the parameter P.1 to P.4 associated with the measurement channel is set to "tESt".
38
Use the
and
buttons to select the measurement channel which you wish to
simulate. Measurement channels 1 to 4 (1/So1 to 4/So4) are possible. For example, if
measurement channel 1 is selected, "1/So1" is displayed to the right in the middle section
of the digital display. "SIMU" is shown in the lower section of the digital display.
and
buttons, set the desired measured value.
Switch to the parameter menu by pressing the <PAR> button for five seconds. The
parameter "P.1" (SoCH1) remains selected.
and
buttons, set the parameter value "on L", "on H", "on_L" or "on_H".
SITRANS DA400 for oscillating positive displacement pumps with protection against explosion
Operating Instructions, 10/2007, A5E00841127-01