Operation
6.4 Parameter menu
Parameter
Parameter
no.
name
P.20
doAL3
P.21
doPR4
P.22
doAL4
P.23
doFAI
P.24
doFAu
P.25
P ouT
P.26
INP1
P.27
INP2
P.28
INP3
P.29
INP4
P.30
AL I1
P.31
AL I2
P.32
AL I3
P.33
AL I4
P.34
do I1
P.35
do I2
P.36
do I3
P.37
do I4
P.38
bUSNr
P.39
APPL
44
Parameter value
As P.15
As P.15
As P.15
As P.15
As P.15
PoS / inv
oFF
24 V
¬24 V
0-20
4-20
20-0
20-4
noPA
As P.26
As P.26
As P.26
-5.0% to 105.0%
-5.0% to 105.0%
-5.0% to 105.0%
-5.0% to 105.0%
oFF, do1, do2, do3, do4, do5,
do6, ¬do1, ¬do2, ¬do3, ¬d04,
¬do5, ¬do6
As P.34
As P.34
As P.34
0 to 126
tYP1
SITRANS DA400 for oscillating positive displacement pumps with protection against explosion
Factory
Meaning
setting
do3
Main alarm 3
oFF
Pre-alarm 4
do4
Main alarm 4
oFF
Input fault summation signal
oFF
Internal fault summation signal
PoS
Output polarity
oFF
Function of universal input 1:
Without function
24 V digital signal > 7 V -> High, passive
normally open contact closed-> High
¬24 V digital signal < 4.5 V -> High, passive
normally open contact open -> High
Analog signal 0 to 20 mA->0 to 100%
Analog signal 4 to 20 mA->0 to 100%
Analog signal 20 to 0 mA->0 to 100%
Analog signal 20 to 4 mA->0 to 100%
Parameter lock
Function of universal input 2
Function of universal input 3
Function of universal input 4
105.0%
Universal input 1 alarm
(analog current function only)
105.0%
Universal input 2 alarm
(analog current function only)
105.0%
Universal input 3 alarm
(analog current function only)
105.0%
Universal input 4 alarm
(analog current function only)
oFF
Status signal assignment
Universal input 1
oFF
Status signal assignment
Universal input 2
oFF
Status signal assignment
Universal input 3
oFF
Status signal assignment
Universal input 4
126
PROFIBUS address
tYP1
Function of the signal processing
For instrumentation with one sensor per
pump valve Acoustic channels work
independently of each other.
Operating Instructions, 10/2007, A5E00841127-01