Parameter
Parameter
no.
name
P.40
STroK
See also
Parameter lock (Page 46)
6.4.3

Setting parameters

Procedure
The procedure for setting a parameter is as follows:
1. Press the <PAR> button for five seconds to switch to the parameter menu.
2. Select the parameters with the
3. Set the value of the parameter using the
See also
Parameter lock (Page 46)
SITRANS DA400 for oscillating positive displacement pumps with protection against explosion
Operating Instructions, 10/2007, A5E00841127-01
Parameter value
tYP2
tYP3
10 to 500
"MEnu" and "PARAM" are shown in the middle section of the digital display to the left and
right respectively. "MEnu" flashes. After these 5 seconds, the appearance of the digital
display is as shown below.
Note
Adjustment of the parameter value takes effect immediately.
Press the <MEAS> button to return to the measured value display. At this point, the
adjusted parameters are saved to ensure operation even in case of power failure.
If the parameter lock is effective, "noPA" appears in the digital display when you attempt
to make the adjustment and it is not possible to adjust the parameter.
Factory
Meaning
setting
For instrumentation with one sensor per
pump valve Acoustic crosstalk between
suction and pressure valve is identified and
compensated for.
For instrumentation with one sensor per
pump head. Suction and pressure valve of a
pump head are monitored by one sensor.
120
Maximum number of strokes of the pump in
min
-1