ANSI Hardware Installation Manual
Procedure 15
Use the following procedure to connect the grounding cable.
1
2
3

6.4 Rack grounding connection

The 7360 ISAM FX-16 requires a 2 AWG rack frame grounding lug for the rack
grounding connection.
Procedure 16
1
2
Issue: 09
To connect the grounding cable
Route the grounding cable to the right or left side of the shelf.
Connect the dual-lug to the grounding cable connection point as shown in Figure 35.
Danger — Possible risk of personal injury or damage to equipment due
to inaccurate or faulty ground cabling.
Inaccurate grounding connection can cause electric shock or equipment
damage when the rack power is switched on.
Note — The grounding cable nuts should be tightened with a torque of
13.28 to 17.7 lbf-in. (1.5 to 2.0 N.m).
STOP. This procedure is complete.
Rack or frame must be suitably connected to the
Danger 1 —
office grounding network in accordance with Article 250 of the
National Electrical Code (NEC) to ensure UL and CSA
compliance. If outside the United States, ground per local
electrical codes and practices.
Possible risk of personal injury or damage to
Danger 2 —
equipment due to inaccurate or faulty ground cabling.
Inaccurate grounding connection can cause electric shock or
equipment damage when the rack power is switched on.
To connect the rack ground
Prepare the frame grounding cable.
Following local practices, route the grounding cable to the top of the rack.
3HH-12893-AAAA-TCZZA
DRAFT
7360 ISAM FX-16 shelf cabling