Siemens SINAMICS S120 System Manual page 175

High frequency drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Danger of death caused by high discharge currents when the external protective conductor
is interrupted
Drive components conduct high discharge currents via the protective conductor. When the
protective conductor is interrupted, touching live components can result in electric shock,
which can lead to death or serious injuries.
• Ensure that the external protective conductor complies with at least one of the following
Functional equipotential bonding with protective conductor connection
The mounting plate, which is connected with the protective conductor connection of the
control cabinet through a low impedance connection, simultaneously serves as the function
equipotential bonding surface. This means that no additional functional equipotential bonding
is required within the drive line-up.
When installing components on standard mounting rails, the data listed in the table also
apply to the functional equipotential bonding. If only smaller conductor cross-sections are
permissible on components, the largest cross-section must be used (e.g. 6 mm
and SMC). These requirements also apply to distributed components located outside the
control cabinet.
No functional equipotential bonding conductors are required for PROFIBUS inside a control
cabinet. For PROFIBUS connections between different buildings or parts of buildings, a
functional equipotential bonding must be routed in parallel to the PROFIBUS cable. The
following cross-sections must be observed in accordance with IEC 60364-5-54:
● Copper 6 mm²
● Aluminum 16 mm²
● Steel 50 mm²
Additional information about equipotential bonding for PROFIBUS can be found at:
http://www.profibus.com/fileadmin/media/wbt/WBT_Assembly_V10_Dec06/index.html
Note
PROFINET
For installation guidelines and information of protective grounding and equipotential bonding
for all PROFINET types and topologies, refer to DOWNLOADS at:
http://www.profibus.com
High Frequency Drive
System Manual, (SH2), 04/2015, 6SL3097-4AH10-0BP3
WARNING
conditions:
– It is laid protected against mechanical damage.
– For an individual conductor, it has a cross-section of at least 10 mm² Cu.
– As a core of a multi-core cable, it has a cross section of at least 2.5 mm² Cu.
– It has a parallel, second protective conductor with the same cross-section.
– It corresponds to the local regulations for equipment with increased leakage current.
Cables routed in control cabinets or enclosed machine enclosures are considered to
1)
be adequately protected against mechanical damage.
11.5 Protective connections and equipotential bonding
1)
Cabinet design and EMC
for TM31
2
175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents