X21 Ep Terminals/Temperature Sensor Motor Module - Siemens SINAMICS S120 System Manual

High frequency drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

High Frequency Modules
4.3 HF Motor Module
4.3.2.2

X21 EP terminals/temperature sensor motor module

Table 4- 3
X21 EP terminal/temperature sensor
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 172)
Max. connectable cross-section: 1.5 mm
EP terminal
The filter times to debounce terminals X21.3 and X21.4 are set using parameters (see
SINAMICS S120/S150 List Manual). Additional parameter settings are also required in order
to prevent discrepancy errors when performing bit pattern tests (light/dark tests). For
comprehensive information, see the SINAMICS S120 Safety Integrated Function Manual,
Chapter "Controlling the safety functions".
Danger to life due to electric shock when connecting unsuitable voltages
Touching parts and components that are at excessively high voltages can result in death or
severe injury.
• Only connect safety extra-low voltages (PELV/SELV) at terminals "EP +24 V" and
Note
Function of the EP terminals
The function of the EP terminals is only available when Safety Integrated Basic Functions
are enabled.
38
Function
+ Temp
- Temp
EP +24 V (enable pulses)
EP M1 (Enable Pulses)
2
WARNING
"EP M1".
Technical data
Temperature sensors: KTY84–1C130 / PTC / bimetallic
switch with NC contact
Supply voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H: 100 μs
H → L: 1000 μs
The pulse inhibit function is only available when Safety
Integrated Basic Functions are enabled.
System Manual, (SH2), 04/2015, 6SL3097-4AH10-0BP3
High Frequency Drive

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents