ABB COMMANDER 1900 Series Programming Manual page 20

Circular chart recorders
Hide thumbs Also See for COMMANDER 1900 Series:
Table of Contents

Advertisement

...3 BASIC CONFIGURATION LEVEL
3.7 Set Up Analog Output
Information.
• Analog Output – omitted on 1901J (non-upgradeable version).
• Fitted analog outputs – assignable to retransmit any process variable.
• Selectable retransmission range – allows maximum resolution on range of interest.
• Adjustable output range – for non-standard and reversed outputs.
Note. The example below shows analog output 1 set to retransmit part of process variable 1's engineering range (250
to 750°C) as a 4.0 to 20.0mA current output.
Select Analog
Select Output
Output
Source
Output 1
PV1
PV2
PV3
PV4
Output 6
18
Setting Output Ranges
1000°C (Engineering Range High)
750°C (Retransmission Range High)
Range to be
transmitted
250°C (Retransmission Range Low)
0°C (Engineering Range Low)
20.0mA (Output Range High)
4.0mA (Output Range Low)