ABB COMMANDER 1900 Series Programming Manual page 8

Circular chart recorders
Hide thumbs Also See for COMMANDER 1900 Series:
Table of Contents

Advertisement

...3 BASIC CONFIGURATION LEVEL
...3.1 Set Up Input (Process Variable)
rNG–HI
20. 0
I n p u t
T y p e
rtd
o r
tCPL
rNG–LO
4. 0
UNItS
dEG–F
dEG–C
NONE
ENG–HI
1000
6
Input Range High
Set the maximum electrical input value required (in electrical units).
Note. The value set must be within the limits detailed in the table below.
Input Type
Range Low Min.
Millivolts
Volts
Milliamps
Resistance Low
Resistance High
Input Range Low
Set the minimum electrical input value required (in electrical units).
Note. The value set must be within the limits detailed in the above table.
Temperature Units
Select units required.
Engineering Range High
Set the maximum engineering (display) value required.
Note. The value set must be within the limits detailed in the tables below.
Degrees Fahrenheit
Linearizer
Type
Min.
Type B
0
Type E
– 148
Type J
– 148
Type K
– 148
Type N
– 328
Type R & S
0
Type T
– 418
RTD
– 328
Performance accuracy is not guaranteed below 725°F/400°C
thermocouples.
Minimum span below zero Type T 126°F/70°C
Minimum span below zero Type N 189°F/105°C
THC standard DIN 4730 IEC 584
RTD standard DIN 43760 IEC 751
Linearizer Type
5/2
3/2
Square Root
None
Continued on next page.
Range High Max.
0
150
0
5
0
50
0
750
0
9999
Max.
Min. Span
3272
1278
1652
81
1652
90
2372
117
2372
162
3092
576
572
108
1112
45
Engineering Range High and Low
Min.
–9999
Min. Range (Low to High)
5.0
0.1
1.0
20
400
Degrees Celsius
Min.
Max.
Min. Span
– 18
1800
– 100
900
– 100
900
– 100
1300
– 200
1300
– 18
1700
– 250
300
– 200
600
for types B, R and S
Max.
+9999
710
45
50
65
90
320
60
25