ABB ACS355 Series Quick Start Up Manual page 126

Function blocks for siemens plc’s
Hide thumbs Also See for ACS355 Series:
Table of Contents

Advertisement

RESET
BOOL
DONE
BOOL
ERR
BOOL
ERNO
INT
STOPPED
BOOL
RUNNING
BOOL
FAULT
BOOL
WARN
BOOL
EXT_RUN_ENABL
BOOL
E
LOCAL_CTRL
BOOL
EXT_CTRL_LOC2
BOOL
ACT_SPEED
INT
MSW
WORD
MCW
WORD
FALSE = No operation, TRUE = Reset drive fault. After fault reset, a new
rising edge of START is needed before next start.
FALSE = Block execution not finished, TRUE = Block execution finished.
FALSE = No error, TRUE = Error occurred during block execution.
Error code when ERR=TRUE, see SIMATIC online help for SFC14 or
SFC15.
FALSE = Drive is not stopped, TRUE = Drive is stopped.
FALSE=Drive is not running, TRUE = Drive is running and following the
speed reference value.
FALSE = No drive fault active, TRUE = Drive fault active.
FALSE = No drive warning active, TRUE = Drive warning active.
FALSE = No external run enable signal received in the drive, TRUE =
External run enable signal received in the drive.
FALSE = Remote control (normal mode), TRUE = Local control (e.g. drive
control panel or pc tool in local mode)
Actual control place, FALSE = EXT1, TRUE = EXT2.
Drive actual speed: -20000 to 20000. See chapter "Drive configuration" for
scaling.
Drive main status word. See actual fieldbus adapter manual for detailed
description.
Drive main control word. See actual fieldbus adapter manual for detailed
description.