ACS850 More parameters read from drive to PLC

Parameter
Description
52.03 ...
Actual value or
52.12
parameter of drive
51.27
FBA PAR
REFRESH

ACS850 More parameters written from PLC to drive

Parameter
Description
53.03
Parameter of
...53.12
drive
51.27
FBA PAR
REFRESH

Configuring ACS880 drives

Starting ACS880 drives for PROFIBUS DP

1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter 50.01
FBA A Enable to Enable.
3. Select how the drive reacts to a fieldbus communication break with parameter 50.02 FBA A comm
loss func.
Note: This function monitors both communication between the fieldbus master and the adapter
module and communication between the adapter module and the drive.
4. Define the time between communication break detection and the selected action with parameter
50.03 FBA A comm loss t out.
5. Select application-specific values for the rest of the parameters in group 50, starting from 50.04.
6. Set the FPBA-01 configuration parameters in group 51. At the minimum, set the required node
address in parameter 51.02 Node address and the communication profile in 51.05 = 1 (ABB drives).
7. Define the process data transferred to and from the drive in FBA-01 configuration parameter groups
52 and 53.
Note: The adapter module sets the Status word and Control word automatically in parameters 52.01
and 53.01.
8. Validate the settings made in parameter groups 51, 52 and 53 by setting parameter 51.27 FBA par
refresh to Configure.
9. Save the valid parameter values to permanent memory by setting parameter 96.07 Param save to
Save.
10. Set the relevant drive control parameters to control the drive according to the application.
Setting
Comment
GGii
GG = parameter group, ii = parameter index
Example, 0104 = actual current; 0117 = motor temp 1
REFRESH
Updates fieldbus settings (groups 50 to 53)
Setting
Comment
GGii
GG = parameter group, ii = parameter index
Example, 2202 = acceleration time 1
REFRESH
Updates fieldbus settings (groups 50 to 53)