ACS580 Minimum required parameter settings for PROFINET
The minimum required parameter settings based on factory default settings.
Parameter
Description
50.01
FBA A Enable
51.01
FBA A ype
51.02
Protocol/Profile
51.04
IP Configuration
51.05 ...
IP address
51.08
51.09
Subnet CDR
51.27
FBA PAR
REFRESH
52.02
FBA data in2
53.02
FBA data out2
20.01
Ext 1 commands
22.11
Ext1 speed ref1
31.11
Fault reset
selection
(46.01)
Speed scaling
Setting
Enable
Ethernet
PNIO ABB Pro (11)
Static (0)
192.xxx.xx.xx or
any other required
IP address.
24
REFRESH
Act1 16bit (5)
Ref1 16bit (2)
Fieldbus A
FB A ref1
P.06.01 bit 7
[Scale max]
Comment
Activates fieldbus module
Filedbus type
Communication profile ABB drives
-
-
24 For subnet mask 255.255.255.0
Updates fieldbus settings (groups 51 to 55)
Actual speed as Data Word 2 from the drive
Speed reference as Data Word 2 to the drive
Fieldbus interface as source for start and stop
Fieldbus interface as source for speed
reference
Fieldbus interface as source for fault reset
Max speed/frequency scaling value (used in
function block/visualization input
SPEED_REF_MAX). Must be less or equal to
drive parameter max speed/frequency.