ACS800 Minimum required parameter settings for PROFIBUS DP

The minimum required parameter settings based on factory default settings.
Parameter
Description
98.02
COMM.
MODULE LINK
98.07
COMM
PROFILE
51.02
NODE
ADDRESS
51.21
DP MODE
51.27
FBA PAR
REFRESH
10.01
EXT 1
STRT/STP/DIR
11.03
EXT REF1
SELECT
16.04
FAULT RESET
SEL
(11.05)
EXT REF1
MAXIMUM
Setting
Comment
FIELDBUS
Activates fieldbus module
ABB
Communication profile ABB drives
DRIVES
[PB NODE]
PROFIBUS DP node address of the drive
[DP MODE]
1 for DPV1, 0 for DPV0
REFRESH
Updates fieldbus settings (groups 51 to 55)
COMM.CW
Fieldbus interface as source for start and stop
COMM.RE
Fieldbus interface as source for speed reference
F
COMM.CW
Fieldbus interface as source for fault reset
[Scale max]
Max speed/frequency scaling value (used in function
block/visualization input SPEED_REF_MAX). Must be
less or equal to drive parameter max speed/frequency.