6 DEDICATED INSTRUCTIONS

6.12 JP/GP.WRITE

Set
Internal device
data
Bit
Word
(S1)
(S2)
(D1)
(D2)
The following format can be used only when the local station is a Universal model QCPU or an LCPU.
Setting data
Set data
Network number of the local station (1 to 239, 254)
Jn
254: The network designated by the valid module during other station
Start I/O signal of the local station's Ethernet module.
Un
(00 to FE
(S1)
Head device of the local station that stores the control data.
(S2)
Head device of the local station that stores data to be written.
(D1)
Head device of the target station to which data is written.
Local station device that is turned on for one scan by the completion of
(D2)
the instruction.
(D2) + 1 is turned on if the instruction execution completes abnormally.
The local devices and the file register for each program cannot be used as devices used in setting data.
6 - 56
This instruction writes data to word devices of other stations.
Link direct device
File register
Bit
1
1 T, C, D, W, ST, SD or SW can be used.
For SD/SW, data can be written within the setting range allowed for the user.
For details on SD/SW, refer to the manual for the programmable controller
CPU or network module of the target station.
Description
access.
: The higher 2 digits of the 3-digit I/O signal)
H
Applicable device
Intelligent
J \
function module
device U \G
Word
MELSEC-Q/L
Index register
Constant
Zn
K, H
2
Set by (
)
User
Character string
User, system
User
System
Others
Data type
Binary 16 bits
Device name
Bit
6 - 56