Mitsubishi Electric MELSEC iQ-R Series User Manual page 64

Energy measuring module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Section 5 BUFFER MEMORY
5.2.4
Current demand time (Un\G3)
Set a time duration for which the moving average of current demand value is calculated from the measured
current value.
If current demand time is set short, the response to change of current will be quick; however, the fluctuation
range may be too large. Adjust the duration according to the load and purposes.
(1)
Setting procedure
(a) Set current demand time in the buffer memory
・Configurable range: 0 to 1800 (seconds)
・Set the value in seconds.
・If this setting is set to 0 second, the current demand will be the same value as the current.
(b) Operating condition setting request (Yn9) from OFF to ON to enable the setting.
(Refer to "4.2.2(5)".)
(2)
Default value
It is set to [120 seconds].
5.2.5
Electric power demand time (Un\G4)
Set a time duration for which the moving average of electric power demand value is calculated from the
measured electric power value.
If electric power demand time is set short, the response to change of power will be quick; however, the
fluctuation range may be too large. Adjust the duration according to the load and purposes.
(1)
Setting procedure
(a) Set electric power demand time in the buffer memory.
・Configurable range: 0 to 1800 (seconds)
・Set the value in seconds.
・If this setting is set to 0 second, the electric power demand will be the same value as the electric power
demand.
(b) Operating condition setting request (Yn9) from OFF to ON to enable the setting.
(Refer to "4.2.2(5)".)
(2)
Default value
It is set to [120 seconds].
63
RE81WH