Section 5 BUFFER MEMORY
(c) Operating condition setting request (Yn9) from OFF to ON to enable the setting.
(Refer to "4.2.2(5)".)
(2)
Default value
It is set to [0: not monitoring].
5.2.7
Alarm 1 monitoring value (Un\G12, 13), alarm 2 monitoring value (Un\G22, 23)
Set the upper/lower limit monitoring value for the target that was set in alarm 1 monitoring factor and alarm 2
monitoring factor.
(1)
Setting procedure
(a) Set the monitoring values for alarm 1 and 2 in the buffer memory.
Configurable range: -2147483648 to 2147483647
* The unit of the setting value is the same as below which was used for the measuring value of the
monitored target configured in alarm 1 monitoring factor and alarm 2 monitoring factor.
Alarm 1 monitoring factor
Alarm 2 monitoring factor
Current demand upper limit
Current demand lower limit
Voltage upper limit
Voltage lower limit
Electric power demand upper limit
Electric power demand lower limit
Power factor upper limit
Power factor lower limit
(b) Operating condition setting request (Yn9) from OFF to ON to enable the setting.
(Refer to "4.2.2(5)".)
(2)
Default value
It is set to [0].
Unit of alarm 1 monitoring value
and alarm 2 monitoring value
A
-3
×10
V
-3
×10
W
(×10
kW)
-3
%
-3
×10
65