Communication Objects - ABB i-bus EIB Product Manual

Switch actuator modules for the room controller, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
4.4.6

Communication objects

4.4.6.1
Overview of the
objects
4.4.6.2
Detailed description of
the objects
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
No
Function
0/15
Switch
Switches the output directly:
"0": Valve closes
"1": Valve opens
0/15
Control value (PWM)
Determines the control value of the valve via the interpulse ratio (pulse width modulation) of
the output.
1/16
Status switch
Reports the switching state of the valve control (valve is opened / closed).
3/18
Forced operation
Sets the output to a defined state and disables it.
This object is visible if 1-bit forced operation is enabled in the parameters. On receipt of the
value "1", the forced operation function is activated and the output triggers the set valve
position. The forced operation is finished on receipt of the value "0".
4/19
Trigger valve purge
This object is visible if the purge function is enabled in the parameters. On receipt of the
value "1", the valve is opened for the duration of the valve purge. The valve purge is ended
on receipt of the value "0".
5/20
Status valve purge
Indicates that the valve purge is active.
11/26
Telegr. fault thermostat
Indicates a possible fault with the room thermostat.
29
Telegr. status byte
This object provides further information about the operating state of the device (only
Electronic Switch Actuator Modules ES/M 2.x.1).
Object: "Switch": 1 bit (EIS1)
This object is visible if the control of the heating actuator is carried out via a
1-bit object. The output is controlled directly, regardless of whether the valve
is normally open or normally closed.
Telegram value
Object: "Control value (PWM)": 1 byte (EIS6)
This object is visible if the control of the heating actuator is carried out via an
8-bit object e.g. within continuous-action control. The object value [0..255]
determines the control ratio ("interpulse period") of the valve. The valve is
closed at object value 0 and fully opened at object value 255.
Telegram value
Object name
Data type
Output A
1 bit (EIS1)
Output A
1 byte (EIS6)
Output A
1 bit (EIS1)
Output A
1 bit (EIS1)
Output A
1 bit (EIS1)
Output A
1 bit (EIS1)
Output A
1 bit (EIS1)
1 byte (EIS14)
Output A...B
"0"
Valve closes
"1"
Valve opens
"0"
Valve closed
...
"255" Valve fully opened
Flags
CW
CW
CT
CW
CW
CT
CT
CRT
49