ABB i-bus
EIB / KNX
2
Device technology
2.1
SA/M 2.6.1
Switch Actuator Module,
2-fold, 6 A
2.1.1
Technical data
Power supply / Incoming supply
Outputs
Connections
Ambient temperature range
Design
CE norm
© 2004 ABB STOTZ-KONTAKT GmbH
Device technology
The 2-fold Switch Actuator Module is operated in any module slot of the
Room Controller Basis Device. Using relay contacts, it switches two
independent groups of electrical loads such as fluorescent lamps. The
outputs are distinguished by a high switching current.
Both the incoming supply and the internal voltage are supplied via the Room
Controller Basis Device. Contact is automatically established when the
modules are snapped in place.
– Operating voltage
– Incoming supply
– 2 load circuits
– Contact endurance
– Load circuits
– Wire ranges
– Storage
– Transport
– Type of installation
– Housing, colour
– Housing dimensions (WxHxD)
– Weight
– in accordance with the EMC guideline and
the low voltage guideline
made available by the Room Controller Basis
Device, contact made via contact system on
base of module
0...264 V AC, contact established via contact
surfaces at the front
Relay outputs
Max. switching current:
16 A / AC1, 10 A / AC3
Max. continuous current: 6 A
Max. inrush peak current I
:
p
400 A (150 µs), 320 A (250 µs)
7
10
mechanical
5
10
electrical (at 230 V / 16 A / AC1)
2 x three-pole, plug-in screw terminals
2
0.2...2.5 mm
finely stranded
2
0.2...40 mm
single-core
-25 °C ... 55 °C
-25 °C ... 70 °C
For snapping into the
Room Controller Basis Device
Plastic housing, anthracite, halogen-free
49 mm x 42 mm x 93 mm
0.1 kg
5