ABB i-bus EIB Product Manual page 35

Switch actuator modules for the room controller, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
This function is advisable if the sensor sends the object "Switch" cyclically on
the bus. It is recommended that the monitoring period is set slightly higher
than three times the transmission cycle time.
Parameter: "Safety state"
The state which the relay adopts while the safety position is active is set
here. The safety position is automatically cancelled as soon as the device
receives a telegram at the object "Switch" again.
Parameter: "Cyclic monitoring time"
The monitoring time with which the object "Switch" is observed is set here.
35