Commissioning

3.3.4.2 Configuration

COM PROFIBUS
3-18
The IM 308-C interface module or S5-95U/DP master is parameterized with
the COM PROFIBUS software. With more recent versions of COM
PROFIBUS, you should be able to find the CM35 module in the ET 200M
under its order number 6AT1 735-0AA01-0AA0. See figure 3-4.
If you cannot find the CM35, copy the type or GSD files from the configura-
tion package to the appropriate directory of COM PROFIBUS. Which files
must be copied depends on the version of COM PROFIBUS.
With COM PROFIBUS (version £ 3.2): Copy the type files to the direc-
S
tory ²TYPDAT5X.²
With COM PROFIBUS (version ³ 3.3): Copy the GSD files to the direc-
S
tory ²GSD.²
Figure 3-4
Selecting the CM35 module during configuration of the ET 200M
Table 3-7
Type and GSD files
File Name
SI801DV*.200
Type file for IM 153-1
ST801EU*.200
Type file for IM 153-2
SIM801D.GS*
GSD file for IM 153-1
SIM801E.GS*
GSD file for IM 153-2
SIM8071.GS*
GSD file for IM 153-2 FO
*
Identifies the particular language version
Use
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618