6.2.1

Description of the Parameter Data

Period number
Measuring range
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618
When you specify the number of periods, you determine the number of peri-
ods of the input signal during which the measurement is to be performed.
You can specify the number of periods for each channel separately.
Table 6-2
Setting of the number of periods
Variable:
Number of Periods
PeriodNumber_Chan_1
PeriodNumber_Chan_2
PeriodNumber_Chan_3
PeriodNumber_Chan_4
PeriodNumber_Chan_5
PeriodNumber_Chan_6
PeriodNumber_Chan_7
PeriodNumber_Chan_8
By selecting the measuring range, you can also increase the period duration
which is measured.
The parameterized measuring range applies to all channels.
Table 6-3
Setting the reference frequency
Variable:
Parameter
Measuring Range
Block
F_RefFrequency
Note
A change in the F_RefFrequency parameter only takes effect with the first
parameter transfer after a warm restart (power on).
Period Duration Measurement Operating Mode
Parameter
Offset
Data Type
Block
1
2.0
1
3.0
1
4.0
1
5.0
1
6.0
1
7.0
1
8.0
1
9.0
Offset
Data
Type
1
10.0
Byte
Value Range
Byte
1 to 40
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Value Range
0h: 100 kHz (standard)
(655 msec to 1 msec)
77h: 50 kHz
(1310 msec
to 2 msec)
EFh: 25 kHz
(2620 msec
to 4 msec)
6-5