List of important alarms and faults
Axxxxx: Alarm
Fyyyyy: Fault
Table A- 1
The most important alarms and faults
Number
Cause
F07085
Control parameters were compulsorily changed for
the following reasons:
They exceeded dynamic limits due to different
•
parameters.
They are not applicable because of properties of
•
the detected hardware that are not present.
–
Fault value (r0949, interpret as decimal):
Changed parameter number.
–
340: The automatic calculation of the motor
and control parameters was performed (p0340
= 1), because the vector control was later acti-
vated as a configuration (r0108.2).
F07802
Infeed or drive does not reply a 'ready' after an inter-
nal actuation command.
Monitoring time too short.
•
DC link voltage not available.
•
Associated infeed or drive of the reporting compo-
•
nents defective.
Supply voltage incorrectly set.
•
STARTER Getting Started
Getting Started, (GS1) 07/2016, 6SL3097-4AG00-0BP4
Remedy
Not necessary.
No parameter change is necessary as the parameters
have already been limited to a reasonable level.
Extend monitoring time (p0857).
•
Ensure the DC link voltage. Check the DC link
•
voltage. Enable the infeed.
Replace associated infeed or drive of the reporting
•
components.
Check settings of the supply voltage (p0210).
•