Procedure
Step 1 Set UPS parameters.
Figure 5-5 iBOX Settings
Figure 5-6 Basic Param.
Issue 07 (2019-12-30)
The UPS software version UPS5000 V100R003C01SPC408 is used for reference.
On the WebUI and LCD of some UPSs, iBOX is named CIM, and iBAT is named BIM.
UPS LCD
a.
On the UPS LCD home screen, choose System Info > Settings > Battery Settings,
and set Number of battery strings.
b.
On the UPS LCD home screen, choose System Info > Settings > iBOX Settings,
and set Basic Param., Advanced Param., and Batt. String Config.
Copyright © Huawei Technologies Co., Ltd.
5 System Commissioning