Toshiba Adjustable Speed Drive H3 Operation Manual page 39

Variable torque adjustable speed drive
Table of Contents

Advertisement

GROUP:SPECIAL CONTROL PARAMETERS
LIQUID CRYSTAL DISPLAY
START-UP FREQUENCY
END FREQUENCY
RUN FREQUENCY
RUN FREQUENCY
HYSTERESIS
ENABLE JUMP
FREQUENCIES
JUMP FREQUENCY #1
JUMP FREQUENCY #1
BANDWIDTH
JUMP FREQUENCY #2
JUMP FREQUENCY #2
BANDWIDTH
JUMP FREQUENCY #3
JUMP FREQUENCY #3
BANDWIDTH
PWM CARRIER
FREQUENCY
*Items 36 - 41 are available only when Item 35 Adjustment Range option 1 is selected.
TOSHIBA
ITEM
PARAMETER
NO.
DESCRIPTION
31
Start-up frequency
32
End frequency
33
Run frequency
34
Run frequency hysteresis
35
Jump frequency enable
36*
Jump frequency #1
37*
+/- band # 1
38*
Jump frequency #2
39*
+/- band # 2
40*
Jump frequency #3
41*
+/- band # 3
42
PWM carrier frequency for 230V
(.75-30 HP)
PWM carrier frequency for 460V
(1-125 HP)
PWM carrier frequency for 460V
(125-300 HP)
8 - 4
DISPLAY
ADJUSTMENT
RESOLUTION
RANGE
0.0 - 10
0.1/0.01 Hz
0.0 - 30
0.1/0.01 Hz
0.0 - max output freq
0.1/0.01 Hz
0.0 - 30
0.1/0.01 Hz
0: Function OFF
-
1: Function ON *
0.0-Max Output Freq
0.1/0.01 Hz
0 - 30
0.1/0.01 Hz
0.0-Max Output Freq
0.1/0.01 Hz
0 - 30
0.1/0.01 Hz
0.0-Max Output Freq
0.1/0.01 Hz
0 - 30
0.1/0.01 Hz
500 Hz - 10 kHz
0.1kHz
500 Hz - 10 kHz
500 Hz - 5 kHz
FACTORY
PAGE
SETTING
NO.
0.1
9-6
0.1
9-6
0.0
9-6
0.0
9-6
0
9-6
0.0
9-6
0.0
9-7
0.0
9-7
0.0
9-7
0.0
9-7
0.0
9-7
2.2 kHz
9-7